Event enrollments (algorithmic reporting)¶
type: ee (or event-enrollment) creates an Event Enrollment object that monitors the present-value of
another value object of the same device and reports through a notification class, so a point without an
alarm block (e.g. a template's temperature) can still raise alarms:

- type: ee
name: RoomTempWatch
monitored_object: Temperature
event_type: out-of-range
event_parameters: {low_limit: 18, high_limit: 28, deadband: 0.5}
notification_class: RoomAlarms
time_delay: 60
- {type: ee, name: ModeWatch, monitored_object: OperationMode, event_type: change-of-state,
event_parameters: {alarm_values: [Maintenance]}, notification_class: 1, notify_type: event}
| key | meaning |
|---|---|
monitored_object |
name of a value object of the same device (Object_Property_Reference = its present-value) |
event_type |
out-of-range (analog, accumulator excluded) or change-of-state (binary / multi-state) |
event_parameters |
out-of-range: low_limit, high_limit (both required, both always enabled), deadband; change-of-state: alarm_values (state numbers or texts, active / inactive for binary) |
notification_class |
name or instance of a notification-class object in the same device |
time_delay, time_delay_normal |
simulated seconds (default 0 / time_delay); time_delay is the Time_Delay of Event_Parameters |
event_enable |
[to-offnormal, to-fault, to-normal], default all true |
notify_type |
alarm (default) or event |
Event enrollments use the same event state machine, notifications, AcknowledgeAlarm,
GetEventInformation / GetAlarmSummary / GetEnrollmentSummary and web UI (row with badge and Ack,
View → Alarms) as intrinsic reporting. BACnet writes to event-parameters (same event type),
event-enable, notify-type, time-delay-normal and notification-class take effect and are written into
the config; acked-transitions is read-only. The demo configuration's Room-Sensor-101 has one. EDE export
lists event enrollments (object type 9); EDE import skips them with a warning (EDE carries no monitored
object or parameters).
Not supported: the event types floating-limit, change-of-value and all others (their exact algorithms are
specified only in ASHRAE 135), fault detection of event enrollments (no fault state / change-of-reliability),
monitoring objects of other devices or properties other than present-value, changing event-type or
object-property-reference by a BACnet write, and creating / deleting event enrollments with
CreateObject / DeleteObject. A value object monitored by an event enrollment cannot be deleted.