Text messages, private transfer and list element services¶
- ConfirmedTextMessage / UnconfirmedTextMessage received by a simulated device are written to the event
log (kind
text-message: sender address and device, priority, message class, text). A simulated device can send one withPOST /api/devices/{id}/text-message{"message": "...", "address": "100:2", "priority": "normal", "message_class": 5, "confirmed": false}(addressdefault: global broadcast*:*, which cannot be confirmed;message_classa number or text). - ConfirmedPrivateTransfer / UnconfirmedPrivateTransfer are written to the event log (kind
private-transfer). A confirmed request is answered as declared in the device'sprivate_transferlist;result: echo(default) returns the service parameters as the result block,nullno result block, a string / integer / real / boolean that value. Without a matching entry the answer is a ConfirmedPrivateTransfer-Errorservices/optional-functionality-not-supported: the device does support the service, only not that vendor / service number, so the simulator uses this error rather than aunrecognized-servicereject (which would claim the whole service is missing). - AddListElement / RemoveListElement on any writable list property (e.g. notification class
recipient-list, calendar date-list, schedule list-of-object-property-references, life safety zone
zone-members). Elements are decoded with the bacpypes3 property datatype; the new list is written exactly
like a WriteProperty of the whole list (same checks and follow-ups). Elements already in the list are
ignored on add. Errors (Add/RemoveListElement-Error): unknown object / property,
services/property-is-not-a-list(property is not a list),property/property-is-not-an-array(array index given),write-access-denied,invalid-data-type, andservices/list-element-not-foundwith the (1-based) number of the first element that is not in the list on remove. Written back to the config: zone-members, recipient-list (also used for sending notifications at once), date-list and list-of-object-property-references (the schedule writes to the new targets), as with WriteProperty; objects that come from a template are kept as an override entry.
- device_id: 1006
name: Room-Sensor-101
private_transfer:
- {vendor_id: 999, service_number: 1} # result: echo (default)
- {vendor_id: 999, service_number: 2, result: 42} # fixed value
Not supported: vendor-specific meaning of private transfer parameters (they are not decoded), text messages from the router device, and the AddListElement / RemoveListElement rules that only ASHRAE 135 defines for individual properties beyond the checks above.