Each simulated device also serves (bacpypes3 0.1.0 leaves most of these unimplemented or broken on the server
side, so the simulator implements them in sme_bacnet_sim/engine.py / sme_bacnet_sim/devmgmt.py):
- COV increment default (analog objects without
cov_increment): a point with abehavior(it changes every tick) gets 1 % of its span (min/maxof the object, elsemin/maxof the behavior), else a per-unit default (0.1 for °C / kW / kWh / A, 0.5 for % / %RH / V / m³/h, 1 for W / Pa, 5 for ppm / lx / W/m², 0.01 Hz; see_UNIT_COVinsme_bacnet_sim/engine.py), else0; points without a behavior keep0(= any change). Setcov_incrementexplicitly to override. - SubscribeCOV (confirmed / unconfirmed, with lifetime) on all value objects: a notification on a
presentValue change of at least
covIncrement(analog), whether it comes from a behavior, a BACnet write or the UI, and on any status-flags change (alarm, fault, out-of-service). SubscribeCOVProperty on any property, with the client's COV increment (default: the object'scovIncrementfor present-value); the notification carries the property and the status flags. - CreateObject / DeleteObject for value objects (AI/AO/AV/BI/BO/BV/MSI/MSO/MSV, Accumulator, Pulse Converter), by object type (first free
instance) or by object identifier, with optional initial values: object-name, present-value, description,
units / cov-increment (analog), active-text / inactive-text (binary), state-text (multi-state, default
State 1,State 2), out-of-service. A created object is appended to the device'sobjectsin the running config (so Save / Export keep it) and appears in the UI at once. Deleting removes it fromobjects; if the object comes from a template its name is added to the device'sremovedlist, which template expansion skips (remove the name fromremovedto get the template object back; creating an object with that name also drops it fromremoved). Not deletable (object/object-deletion-not-permitted): the device object, network ports, trend logs, schedules, calendars, notification classes, and value objects logged by a trend log or written by a schedule. Errors on create use CreateObject-Error with the failing element number (dynamic-creation-not-supported,object-identifier-already-exists,duplicate-name,write-access-deniedfor other properties,invalid-data-type). - TimeSynchronization / UTCTimeSynchronization (to a device, or to the router / broadcast): moves the
simulated clock so that it shows the received time (UTC is converted with the host's time zone); the
elapsed simulated time keeps running, schedules are re-evaluated at once and trend logs continue on the new
clock. Simulation → Sync to PC clock (or
POST /api/simulation {"set_time": ...}) does the same from the UI. - DeviceCommunicationControl enable / disable / disable-initiation with an optional time duration in minutes, measured on the wall clock (the duration is a real-world timeout in the standard, independent of the simulation speed). While disabled the device ignores everything except DeviceCommunicationControl and ReinitializeDevice and sends nothing (no I-Am, COV or event notifications); disable-initiation still answers requests and Who-Is but initiates nothing else. The device header in the UI shows the state with an Enable communication button.
- ReinitializeDevice warmstart: values back to the configured initial values, priority arrays
relinquished, out-of-service cleared, behaviors and alarms (event state normal, all acknowledged) reset,
communication re-enabled. Coldstart: the same, and trend-log buffers are cleared. Other states return
services/optional-functionality-not-supported.
Device keys for these services:
- device_id: 1002
name: AC-1F-East
dcc_password: secret # DeviceCommunicationControl password (default: none = not checked)
reinit_password: boot # ReinitializeDevice password (default: none = not checked)
removed: [FilterAlarm] # template objects deleted with DeleteObject (written by the simulator)
A wrong password returns security / password-failure.