Accumulators, pulse converters and loops

- {type: acc, name: EnergyPulses, units: kilowatt-hours, scale: 0.01, max: 99999999,
   behavior: {type: pulse, rate: "ActivePower * 100 / 3600"}}
- {type: pc, name: EnergyFromPulses, input_object: EnergyPulses, scale_factor: 0.01, units: kilowatt-hours}
- type: loop
  name: SupplyTempLoop
  controlled_object: SupplyTemp      # controlled-variable-reference (present-value)
  manipulated_object: CoolValve      # manipulated-variable-reference (present-value)
  setpoint_object: SupplyTempSP      # or a fixed setpoint: 16
  proportional_constant: 8
  integral_constant: 0.2
  min: 0                             # minimum-output
  max: 100                           # maximum-output
  units: percent                     # output-units
  priority_for_writing: 10
Type Keys
acc (Accumulator, 23) value (unsigned count), units, scale (Scale as a float scale, default 1), max (Max_Pres_Value, default 4294967295; above it the count wraps to 0), prescale ([multiplier, modulo_divide])
pc (Pulse Converter, 24) value, units, scale_factor (default 1), input_object (an accumulator of the same device → Input_Reference), cov_increment
loop (Loop, 12) controlled_object, manipulated_object, setpoint or setpoint_object, proportional_constant (default 1), integral_constant (1/s, default 0), derivative_constant (s, default 0), bias (default 0), action (direct / reverse, default direct), update_interval (sim seconds, default 1; the Update_Interval property is in ms), min / max (output limits, default 0 / 100), units (Output_Units), priority_for_writing (default 16), cov_increment
  • Accumulator: driven by any behavior; the pulse behavior adds rate pulses per second.
  • Pulse converter with input_object: every tick the accumulator's count delta (wrap-around included) times Scale_Factor is added to Present_Value, and Count shows the accumulator's count. Without input_object it is a plain Real value object (behaviors apply).
  • Loop (textbook PID, on the simulated clock every Update_Interval): e = PV − setpoint (direct) or setpoint − PV (reverse); output = bias + Kp·e + Ki·∫e dt + Kd·de/dt, clamped to Minimum_Output .. Maximum_Output, with the integral held while the output is saturated (anti-windup). The output goes to the loop's Present_Value and to the manipulated object (its priority array at Priority_For_Writing when it is commandable, else its present value). Constants, setpoint, action, limits, update interval and write priority can be changed with WriteProperty. With a setpoint_object, Setpoint follows that object's value. Out of service: no computation and no output write. The UI shows the output plus PV / SP.
  • COV: pulse converters use the COV-increment criteria, loops the generic criteria (present-value / status-flags), as defined by bacpypes3. bacpypes3 has no COV criteria for the Accumulator, so SubscribeCOV on an accumulator is not available (SubscribeCOVProperty works).
  • CreateObject creates accumulators and pulse converters (without input reference); loops are declared in the config only. DeleteObject refuses objects referenced by a pulse converter or loop.
  • EDE: accumulators and pulse converters are exported (unit code; the max column of an accumulator is Max_Pres_Value) and imported; loops are exported but skipped on import with a warning (EDE carries no references / PID constants).

Not supported: applying Prescale (stored only), Value_Set / Value_Before_Change / Value_Change_Time / Logging_Record / Pulse_Rate and limit monitoring of the Accumulator; the Adjust_Value semantics of the Pulse Converter (it is a plain writable property: Count and Present_Value are not adjusted), Count_Before_Change / Count_Change_Time / Update_Time and COV_Period periodic notifications; intrinsic reporting on these three types (alarm is rejected); references to other devices or to properties other than Present_Value.