Trend logs

type: tl (or trend-log) creates a BACnet Trend Log object that logs another object of the same device (polled or on change) and keeps the samples in a ring buffer (oldest records are dropped, stop-when-full is false):

- {type: tl, name: RoomTemp_Log, log_object: RoomTemp, log_interval: 60, buffer_size: 1000}
- {type: tl, name: RoomTemp_Cov, log_object: RoomTemp, logging_type: cov, client_cov_increment: 0.5}
Key Default Notes
log_object (required) name of the logged object; must exist in the device
log_property present-value any numeric / enumerated / boolean property of the target
log_interval 60 simulated seconds (BACnet log-interval is reported in 1/100 s); polled mode only
logging_type polled polled or cov (BACnet logging-type)
client_cov_increment target's cov-increment cov mode only; minimum change of a real value that is logged
buffer_size 1000 ring buffer size
enabled true initial value of the enable property (also writable over BACnet and from the UI)

Samples are taken on the simulated clock and time-stamped with the simulated date/time, so with time_scale: 3600 an hour of real time yields a day of history at the configured interval. When one tick is longer than log_interval, the missed intervals collapse into one sample. Read the buffer with ReadRange (by position, by sequence number, by time, or without a range for everything that fits in the response); log-buffer is not readable with ReadProperty. Writing 0 to record-count clears the log. The split_ac and power_meter templates include one trend log each. EDE export / import carries trend logs (see EDE below).

COV logging (logging_type: cov): instead of sampling on an interval, a record is appended whenever the logged value has changed since the last record by at least the increment — client_cov_increment if set (read back as client-cov-increment), else the target's cov-increment when logging its present value, else any change; boolean / enumerated / integer values log on any change — or when the target's status flags change. The first record is taken as soon as the log is enabled with an empty buffer (also after clearing). Changes are detected once per simulation tick and stamped with the simulated clock; log-interval reads 0. Not supported: the triggered logging type, logging objects of other devices (and therefore COV subscriptions to them / cov-resubscription-interval), and log-status / time-change records in the buffer.