Not supported

Foreign device registration (cross-subnet)

Not supported: combining foreign_device with mode: bbmd, BBMD host names (IPv4 literals only), and reading or editing the BBMD's tables (Read-Broadcast-Distribution-Table, Read-Foreign-Device-Table and similar).

Accumulators, pulse converters and loops

Not supported: applying Prescale (stored only), Value_Set / Value_Before_Change / Value_Change_Time / Logging_Record / Pulse_Rate and limit monitoring of the Accumulator; the Adjust_Value semantics of the Pulse Converter (it is a plain writable property: Count and Present_Value are not adjusted), Count_Before_Change / Count_Change_Time / Update_Time and COV_Period periodic notifications; intrinsic reporting on these three types (alarm is rejected); references to other devices or to properties other than Present_Value.

Files and programs

Not supported: the transitional states loading, waiting and unloading, rejecting requests that are not valid in the current state, any real program execution or failure (Reason_For_Halt other than normal), writing File_Size to truncate a file, the Archive semantics (plain writable flag) and a consistency check of the request's Record_Count against the records sent; the exact rules exist only in the paid ASHRAE 135 text.

Trend logs

Not supported: the triggered logging type, logging objects of other devices (and therefore COV subscriptions to them / cov-resubscription-interval), and log-status / time-change records in the buffer.

Schedules and calendars

Not supported: writing to targets on devices outside the simulator (no network WriteProperty).

Alarms (intrinsic reporting)

Not supported: acknowledgment notifications (notify type ack-notification). AcknowledgeAlarm is answered and updates Acked_Transitions, but no notification is sent to recipients. Exact all-or-nothing semantics of WritePropertyMultiple beyond the up-front validation above (rollback of already applied writes). SME BACnetSim is free and is built from public sources only; behaviors that can only be specified from the paid ASHRAE 135 text are left out.

Event enrollments (algorithmic reporting)

Not supported: the event types floating-limit, change-of-value and all others (their exact algorithms are specified only in ASHRAE 135), fault detection of event enrollments (no fault state / change-of-reliability), monitoring objects of other devices or properties other than present-value, changing event-type or object-property-reference by a BACnet write, and creating / deleting event enrollments with CreateObject / DeleteObject. A value object monitored by an event enrollment cannot be deleted.

Life safety points and zones

Not supported: change-of-life-safety event reporting (alarm-values, life-safety-alarm-values, fault-values and the event properties are not evaluated), the severity order of the states and mode-dependent transitions, maintenance-required / direct-reading / setting behaviour, and creating / deleting life safety objects with CreateObject / DeleteObject.

Text messages, private transfer and list element services

Not supported: vendor-specific meaning of private transfer parameters (they are not decoded), text messages from the router device, and the AddListElement / RemoveListElement rules that only ASHRAE 135 defines for individual properties beyond the checks above.