Life safety points and zones¶
- {type: lsp, name: Smoke-101, description: Smoke detector} # life-safety-point (object type 21)
- type: lsp
name: Heat-101
value: quiet # initial state (BACnetLifeSafetyState: quiet, pre-alarm, alarm, fault, ...)
mode: "on" # BACnetLifeSafetyMode (default on; quote on / off in YAML)
accepted_modes: ["on", "off", test] # default [off, on, test]
operation_expected: none # BACnetLifeSafetyOperation, read-only (default none)
silenced: unsilenced # initial BACnetSilencedState
behavior: {type: random_alarm, probability: 0.001, state: alarm} # optional, per sim second
- {type: lsz, name: Zone-101, zone_members: [Smoke-101, Heat-101]} # life-safety-zone (object type 22)
The simulator uses a simplified model (the full state machine is only specified in ASHRAE 135):
- Tracking_Value is the live detector state. Set it from the UI (detector-state menu of the row,
POST /api/devices/{id}/life-safety/{type:instance}/state) or with the optionalrandom_alarmbehavior (goes tostateat random, back toquieton the next tick). It is read-only for BACnet clients. - Present_Value follows Tracking_Value while that is not
quietand stays latched when it returns toquiet, until a reset. BACnet writes to present-value are only accepted while out-of-service. - Zone: its Tracking_Value is the present value of the first member (in Zone_Members order) that is not
quiet, elsequiet. This is a simplification: no severity order between the states is applied. - LifeSafetyOperation:
silence/silence-audible/silence-visualset andunsilence*clear the audible / visible part of Silenced;reset/reset-alarm/reset-fault(all the same here) copy Tracking_Value to Present_Value and unsilence;nonedoes nothing. An operation on a zone also acts on its members; without an object identifier it acts on every life safety object of the device. Vendor-specific operations returnservices/optional-functionality-not-supported, other object typesobject/unsupported-object-type. Every operation is written to the event log. - Mode is writable but must be one of accepted-modes (else
property/value-out-of-range); zone-members is writable (WriteProperty, AddListElement / RemoveListElement) and written back to the config as member names (references to other devices are ignored). - ReinitializeDevice restores the configured state. EDE export lists them (object type 21 / 22, state number as value); EDE import keeps type, name and state.
Not supported: change-of-life-safety event reporting (alarm-values, life-safety-alarm-values, fault-values and the event properties are not evaluated), the severity order of the states and mode-dependent transitions, maintenance-required / direct-reading / setting behaviour, and creating / deleting life safety objects with CreateObject / DeleteObject.