Behaviors¶
type |
Parameters | Example |
|---|---|---|
sine |
min max period phase noise |
daily or periodic swings |
random |
min max |
uniform noise |
random_walk |
min max step |
drifting sensor |
expr |
expr |
"Zone1_Cmd", "1.732 * Voltage * Current * PowerFactor / 1000" |
follow |
target tau noise |
first-order lag to a target: "SetPoint if OnOff else 30" |
counter |
rate |
integrates units/second: "Power / 3600" → kWh |
pulse |
rate |
accumulator pulses per second (fractions carried over): "ActivePower * 100 / 3600" |
replay |
file column interpolate loop offset |
play a CSV time series (below) |
CSV replay (replay): the first CSV column is the timestamp — elapsed time (HH:MM:SS or seconds) or an
ISO datetime — and every other column is a value series. Each point names the file and its column, so one CSV
can drive many points (the file is parsed once). Relative paths resolve against the config file's directory.
Replay time 0 is the first row and advances with the simulated clock, so it follows simulation.time_scale.
interpolate: linear (default) or step (hold the previous row); binary and multi-state points always step-hold
(active / inactive / 1 / 0, state numbers). offset starts mid-file ("06:00:00", seconds, or an ISO
datetime for ISO CSVs); loop: true repeats, otherwise the last value is held. An empty cell holds the previous
value. Bad timestamps, rows going backwards or an unknown column are reported when the config is loaded. The
point row shows the replay position, e.g. replay 06:12:30 (26%). Example: configs/replay-example.yaml with
configs/data/day-profile.csv:
time,oat,rh,occupied,mode
00:00:00,13.8,71,inactive,1
08:00:00,17.2,64,active,2
19:00:00,20.2,56,inactive,1
24:00:00,13.8,71,inactive,1
- {type: ai, name: OutdoorTemp, units: degreesCelsius,
behavior: {type: replay, file: data/day-profile.csv, column: oat, loop: true, offset: "06:00:00"}}
- {type: bi, name: Occupied,
behavior: {type: replay, file: data/day-profile.csv, column: occupied, loop: true, offset: "06:00:00"}}
CSV can be recorded from a real device (read-only) with sme-bacnet-sim record, see Cloning.
Expressions are sandboxed Python expressions. Available names: the device's object names, t (sim seconds),
dt, hour (sim clock, 0–24), pv("Device", "Object") to read another device, and
sin cos exp log sqrt pi abs min max round clamp random uniform noise gauss.
Objects that are out of service stop following their behavior, which is how you inject a fixed value or a fault. Writing a simulated input from the UI sets it out of service automatically.
Templates¶
lighting, split_ac, ahu, power_meter, env_sensor, pv_inverter, custom — see