跳转至

事件登记(Event Enrollment,algorithmic reporting)

type: ee(或 event-enrollment)创建 Event Enrollment 对象:监视同一设备中另一个值对象的 present-value, 并通过 Notification Class 发送通知,因此没有 alarm 块的点(例如模板里的温度)也能产生报警:

处于报警状态的 Event Enrollment、Notification Class 与 Life Safety

- type: ee
  name: RoomTempWatch
  monitored_object: Temperature
  event_type: out-of-range
  event_parameters: {low_limit: 18, high_limit: 28, deadband: 0.5}
  notification_class: RoomAlarms
  time_delay: 60
- {type: ee, name: ModeWatch, monitored_object: OperationMode, event_type: change-of-state,
   event_parameters: {alarm_values: [Maintenance]}, notification_class: 1, notify_type: event}
键 含义
monitored_object 同一设备中值对象的名称(Object_Property_Reference = 其 present-value)
event_type out-of-range(模拟量,不含 Accumulator)或 change-of-state(二进制 / 多态)
event_parameters out-of-range:low_limit、high_limit(均必填、始终启用)、deadband;change-of-state:alarm_values(状态编号或文本,二进制用 active / inactive)
notification_class 同一设备中 notification-class 对象的名称或实例号
time_delay、time_delay_normal 模拟秒(默认 0 / time_delay);time_delay 即 Event_Parameters 中的 Time_Delay
event_enable [to-offnormal, to-fault, to-normal],默认全部 true
notify_type alarm(默认)或 event

事件登记与 intrinsic reporting 共用同一套事件状态机、通知、AcknowledgeAlarm、 GetEventInformation / GetAlarmSummary / GetEnrollmentSummary 以及 Web UI(带徽标和 确认 按钮的行、视图 → 报警)。 对 event-parameters(同一事件类型)、event-enable、notify-type、time-delay-normal、notification-class、event-enrollment 的 BACnet 写入会生效并写回配置;acked-transitions 只读。演示配置的 Room-Sensor-101 中有一个示例。EDE 导出包含事件登记 (对象类型 9);EDE 导入会跳过并给出警告(EDE 不含监视对象和参数)。

Not supported:事件类型 floating-limit、change-of-value 及其它所有类型(其精确算法仅在 ASHRAE 135 中规定)、 事件登记的故障检测(无 fault 状态 / change-of-reliability)、监视其它设备的对象或 present-value 以外的属性、 通过 BACnet 写入修改 event-type / object-property-reference、用 CreateObject / DeleteObject 创建 / 删除事件登记。 被事件登记监视的值对象不能删除。