A configuration file is YAML with three sections: simulation, listeners and devices. The demo is configs/demo-site.yaml; sme-modbus-sim validate FILE checks a file without starting anything.

simulation: {tick_seconds: 1, time_scale: 1, history_size: 600, running: true}

listeners:
  - {id: tcp1, type: tcp, host: 0.0.0.0, port: 5020, unit_id_mode: strict, unknown_unit: ignore}
  - {id: gw1, type: rtu_over_tcp, host: 0.0.0.0, port: 5021}

devices:
  - name: Meter-1
    unit_id: 3
    template: power_meter
    word_order: little
    points:
      - {name: serial_number, value: "MTR00001"}

simulation

Key Meaning
tick_seconds Behavior update interval in seconds (above 0.05, up to 60)
time_scale Simulated seconds per real second (above 0, up to 3600)
history_size Samples kept per point for the UI chart
running Start running or paused

listeners

Key Meaning
id Name used by devices[].listeners
type tcp (Modbus TCP, MBAP), udp (Modbus TCP / MBAP frames in UDP datagrams), tls (Modbus/TCP Security: MBAP over TLS), rtu_over_tcp (RTU frames with CRC-16 over a TCP socket) rtu (serial line, RTU) or ascii (serial line, Modbus ASCII)
host, port tcp / rtu_over_tcp: bind address and TCP port (default 5020; ports below 1024 need privileges). udp: bind address and UDP port (1-65535, default 5020). tls: bind address and TCP port (default 8020; the registered port is 802). rtu / ascii: port is the serial device (COM5, /dev/ttyUSB0) or a pyserial URL (socket://host:port, rfc2217://...), or pty (see below); host is ignored
unit_id_mode strict: only configured unit IDs answer. any: every unit ID is routed to default_unit
unknown_unit In strict mode: ignore (no response, like a real bus) or exception (gateway exception)
default_unit Unit ID used by any mode and for TCP / UDP unit IDs 0 / 255
baudrate, bytesize, parity, stopbits rtu / ascii only. Defaults 19200 (spec default), 8 (ascii: 7), E, 1. rtu needs 8 data bits; ascii accepts 7 or 8. parity: E / O / N; with N the default is 2 stop bits (Serial Line V1.02). N + stopbits: 1 is accepted as a common but non-conforming setting
strict_timing rtu only (default false). true: a gap longer than t1.5 inside a frame drops it and exactly t3.5 ends a frame. false: no t1.5 check and frames end after max(t3.5, 20 ms) of silence, because USB-serial adapters deliver bytes in bursts
char_timeout ascii only (default 1 s). An unfinished frame is dropped when no character arrives for this long
link port: pty only. Path of a symlink to the device under test's end of the pty pair (e.g. /tmp/ttyV0)

Modbus UDP (type: udp)

listeners:
  - {id: u1, type: udp, host: 0.0.0.0, port: 5020}
  • Each datagram carries exactly one Modbus TCP (MBAP) ADU; the answer is sent to the source address of the datagram with the transaction id echoed. The simulator never retransmits.
  • No Modbus specification defines Modbus over UDP; ModbusSim follows common practice (for example modpoll -m udp and the pymodbus UDP client).
  • A datagram shorter than 8 bytes, whose MBAP length field does not match the datagram length, or whose protocol id is not 0 is dropped (shown in the trace as dropped, with the reason); the listener keeps serving.
  • Unit routing (unit_id_mode, unknown_unit, default_unit, unit IDs 0 / 255) is the same as for tcp. Serial-only keys are rejected as for tcp.
  • A udp and a tcp listener may use the same host:port; two udp listeners on the same host:port are rejected.
  • UDP has no connections: the client count in the stats and the UI is the number of distinct source addresses seen in the last 60 s.

Modbus/TCP Security (type: tls)

listeners:
  - id: secure
    type: tls
    port: 8020
    certificate: pki/server.crt
    private_key: pki/server.key
    ca: pki/ca.crt
    roles:
      operator: all
      viewer: read
      tuner: [3, 6, 16]
  • MBAP over TLS, following "MB-TCP-Security v36 (2021-07-30)". The default port is 8020 (the registered port is 802; 8020 needs no privileges, like 5020 for 502).
  • Keys, valid for type: tls only. Relative paths are relative to the configuration file.
Key Meaning
certificate Server certificate (PEM, may contain the chain). Required
private_key Private key of the server certificate (PEM)
ca CA certificates (PEM) used to verify client certificates
client_auth Default true: a client certificate is required (spec R-07 / R-08), so ca is required too. false: the client certificate is optional
crl Optional CRL (PEM); it checks the leaf client certificate. Needs ca
roles Map role -> all, read or a list of function codes (1-127). Needs ca
  • TLS 1.2 is the minimum, TLS 1.3 is allowed. TLS 1.2 cipher suites are limited to ECDHE with AES-GCM or ChaCha20 (this includes the mandatory TLS_ECDHE_RSA_WITH_AES_128_GCM_SHA256); no compression. The client host name is not checked (the specification defines no check).
  • Role. The role is read from the client certificate extension with OID 1.3.6.1.4.1.50316.802.1 (a UTF8String). The extension must be non-critical: OpenSSL rejects a certificate with an unknown critical extension, so the handshake fails (CERTIFICATE_VERIFY_FAILED).
  • Authorization. Without roles there is no authorization. With roles, a listed role gets its rights; an unlisted role, or a certificate without a role, may only read (FC 01, 02, 03, 04 and 2B/0E). A refused request is answered with exception 01 (Illegal Function, spec R-31) and traced as an rx event with the error not authorized (role 'x') or not authorized (no role); the connection stays open. Authorization works by function code only (the specification's inputs are role and function code), not by address range, and it is checked before fault injection.
  • A failed handshake is traced as the rx event "TLS handshake failed" with the reason, and the connection is closed. Faults apply as on tcp.
  • Read-only client: sme-modbus-sim scan / record with --transport tls --host H [--port 802] [--ca ca.crt] [--cert client.crt --key client.key]. The default port is 802; without --ca the server certificate is not verified. In the Web UI and the API the target keys are ca, certificate and private_key (the three inputs are shown for type tls only).

Test PKI with openssl (a test CA, a server certificate and a client certificate with the role operator):

# For testing only. Needs openssl; on Windows run it in Git Bash (add: export MSYS_NO_PATHCONV=1).
mkdir pki && cd pki
cat > ext.cnf <<'EOF'
[server]
basicConstraints = CA:FALSE
subjectAltName = DNS:localhost,IP:127.0.0.1
extendedKeyUsage = serverAuth
[client]
basicConstraints = CA:FALSE
extendedKeyUsage = clientAuth
1.3.6.1.4.1.50316.802.1 = ASN1:UTF8String:operator
EOF
# test CA
openssl req -x509 -newkey rsa:2048 -nodes -keyout ca.key -out ca.crt -days 365 -subj "/CN=Test CA" \
  -addext "basicConstraints=critical,CA:TRUE" -addext "keyUsage=critical,keyCertSign,cRLSign"
# server certificate
openssl req -newkey rsa:2048 -nodes -keyout server.key -out server.csr -subj "/CN=localhost"
openssl x509 -req -in server.csr -CA ca.crt -CAkey ca.key -CAcreateserial -out server.crt -days 365 \
  -extfile ext.cnf -extensions server
# client certificate carrying the role "operator"
openssl req -newkey rsa:2048 -nodes -keyout client.key -out client.csr -subj "/CN=operator1"
openssl x509 -req -in client.csr -CA ca.crt -CAkey ca.key -CAcreateserial -out client.crt -days 365 \
  -extfile ext.cnf -extensions client

Serial RTU (type: rtu)

listeners:
  - {id: com1, type: rtu, port: COM5, baudrate: 19200, parity: E}
  • Frame end = silence of t3.5 (3.5 character times of 11 bits; fixed 1.75 ms above 19200 baud); requests of known length are answered without waiting for the silence.
  • Unit IDs 1-247 answer as configured; 0 is broadcast (write function codes run on every device of the listener, never answered); 248-255 are ignored.
  • unknown_unit: exception has no effect on a serial line (unknown units never answer).
  • If the port cannot be opened, the listener reports status: error in /api/state and the other listeners keep running; a configuration reload retries.

Serial ASCII (type: ascii)

listeners:
  - {id: com2, type: ascii, port: COM6}   # 19200 baud, 7E1
  • Frame = :, address, PDU and LRC as hex characters, then CR LF (Serial Line V1.02 section 2.5.2). Lower-case hex is accepted; responses use upper case.
  • Characters before : are ignored; a new : discards an unfinished frame, as does a gap longer than char_timeout. A bad LRC, an odd number of hex characters or a frame over 513 characters gets no response.
  • port: pty works for ASCII too. Addressing, broadcast and fault injection are as for RTU; corrupt_crc inverts the LRC.

Pseudo-terminal pair (port: pty)

On Linux, macOS and WSL2 ModbusSim can create the virtual serial port pair itself, with no driver and no root:

listeners:
  - {id: vcom, type: rtu, port: pty, link: /tmp/ttyV0}
  • ModbusSim keeps one end of the pair; the device under test opens link (or the /dev/pts/N path shown in the log, the UI and /api/state as device) as its serial port.
  • link is created at startup and removed on exit. If the path already exists, the listener reports status: error and the existing file is left alone. Put it in a directory you can write to (/dev needs root).
  • The device under test may close and reopen the port at any time.
  • Limits: a pty carries no RTS / CTS / DTR, ignores the baud rate and parity, and does not pace bytes, so t1.5 / t3.5 cannot be tested; keep strict_timing: false.
  • The device under test must open the pty as 8N1: on Linux (tested on the WSL2 5.15 kernel), setting even/odd parity or 7 data bits on a pty fails with EINVAL. The bytes are the same either way, so an ASCII or 8E1 master still works once its serial settings are 8N1.
  • Not available on Windows: configuration validation fails and suggests a signed virtual serial port driver, a pair of USB-RS485 adapters, or rtu_over_tcp.

Function codes

01, 02, 03, 04, 05, 06, 0F, 10, 16 (mask write register), 17 (read/write multiple registers, write before read) and 2B / 0E (Read Device Identification: read codes 01 basic, 02 regular, 03 extended stream, 04 individual; long answers use More Follows). Serial listeners also answer 07, 08, 0B, 0C and 11 (see below). Writes through 16 / 17 pass the same checks as 06 / 10 (read-only points, partial multi-register values, min / max). Other function codes answer exception 01.

Serial diagnostics (FC 07 / 08 / 0B / 0C / 11)

Serial listeners (rtu, ascii) also answer the "Serial Line only" function codes. TCP, UDP and RTU over TCP answer them with exception 01.

FC Answer
07 Read Exception Status 00
08 Diagnostics sub-functions 00 echo (data of any length), 01 restart communications (data 0000 keeps the event log, FF00 clears it), 02 diagnostic register (always 0), 03 change ASCII input delimiter, 04 force Listen Only Mode (no answer), 0A clear counters, 0B-12 counters, 14 clear overrun counter
0B Get Comm Event Counter status 0000 (never busy) and the event counter
0C Get Comm Event Log status, event counter, bus message count and up to 64 event bytes, newest first
11 Report Server ID the device's identification.product_code as Server ID, run indicator FF, no additional data

Counters are 16 bit, wrap around and start at 0 when the listener starts.

  • Per listener (the line): bus message (08/0B, every correct frame whatever its address), bus communication error (08/0C, CRC or LRC errors, frames too short, invalid characters, timeouts), character overrun (08/12, always 0: the simulator never loses characters).
  • Per device on the listener: exception (08/0D, also errors in broadcasts, which are never answered), server message (08/0E, own and broadcast requests), no response (08/0F, broadcasts and requests left unanswered because of Listen Only Mode or a no_response / disconnect fault), NAK (08/10, exception 07), busy (08/11, exception 06, for example from the busy fault), the FC 0B event counter and the FC 0C event log.

Where the specifications are silent or disagree, ModbusSim does this:

  • Sub-functions 05-09 answer exception 03; 13 and 15 or above answer exception 01.
  • 01 and 0A also clear the bus counters of the listener. 0A does not clear the event log.
  • Listen Only Mode: requests are still counted and logged but not executed or answered; only 08/01 is executed, still without an answer. The event byte for entering the mode is 04. Broadcast writes skip a device in Listen Only Mode.
  • A broadcast executes only write function codes; any other function code in a broadcast (diagnostics included) is not executed and counts as an exception.
  • The event counter counts every request completed without an exception, broadcasts included, except FC 0B and 0C.
  • 03 changes only the delimiter the listener expects at the end of ASCII requests (one setting per listener, shared by its devices); answers still end with CR LF. 01 restores LF. On an RTU listener 03 is echoed and has no effect.
  • Fault injection: an exception or busy fault counts like the real exception; no_response counts as not answered.

devices

Key Meaning
name, description Device name (unique) and free text
unit_id 1-247
listeners Listener IDs this device is attached to (default: all)
template, params Generate points from a template, see Behaviors & templates
byte_order, word_order Device defaults: big or little
undefined_address exception (illegal data address, default) or zero for reads outside defined points
identification vendor_name, product_code, revision, vendor_url, product_name, model_name, user_application_name (served by FC 2B / 0E; defaults SmartEdge, SME-MODBUS-SIM, program version)
points Points of this device; entries with the name of a template point override it
removed Template points deleted by the user

points

Key Meaning
name, description, units Identification
table coil, discrete, input or holding
address 0-based protocol address; omitted addresses are allocated automatically
datatype bool, bit, uint16, int16, uint32, int32, float32, uint64, int64, float64, string, enum
count Registers of a string (two characters each)
bit Bit number 0-15 for datatype: bit (one bit of a holding / input register)
byte_order, word_order Override the device defaults
scale, offset Register value = (engineering value - offset) / scale
access r or rw; writes to r points return exception 02
value Initial value
min, max Clamp the value
labels enum mapping, raw value to label (quote labels such as "ON")
behavior See Behaviors & templates

Byte order and word order

For multi-register values, word_order decides which register comes first and byte_order the byte order inside a register. A float32 of 1.0 (0x3F800000) is sent as:

byte / word order Registers Name
big / big 3F80 0000 ABCD (Modbus standard)
big / little 0000 3F80 CDAB (common for meters)
little / big 803F 0000 BADC
little / little 0000 803F DCBA

Coupled site example

configs/demo-coupled-site.yaml couples five devices on one TCP listener (port 5020) with generic templates and expressions only, so an EMS can close the loop against it:

Device (unit) Point Behavior
PV-1 (1, custom) p_ac 40 * max(0, sin(pi * (hour - 6) / 12)) * cloud_factor (daylight 06:00-18:00; cloud_factor is a random walk 0.7-1.0)
Load-1 (2, custom) active_power 20 + 15 * exp(-((hour - 8) ** 2) / 4) + 25 * exp(-((hour - 19) ** 2) / 6) + noise(0.5)
PCS-1 (3, battery_pcs) p_actual Ramps to p_setpoint at 10 kW/s while run_command is on (blocked at the BMS SOC limits)
BMS-1 (4, bms) soc Counter with rate -p_actual / capacity_kwh * 100 / 3600 (% per second), clamped 0-100
Meter-1 (5, power_meter) active_power pv('Load-1', 'active_power') - pv('PV-1', 'p_ac') - pv('PCS-1', 'p_actual')

Signs: PCS power is + discharge / - charge; meter power is + import / - export, and its import / export energy counters integrate it. Behaviors run device by device in file order, so the meter (listed last) uses values of the same tick. Try: write holding 0 = 200 (20.0 kW) and coil 0 = 1 on unit 3, then watch the meter import fall by 20 kW and BMS-1 soc decrease.