Behaviors & templates

Behaviors

A point with a behavior is updated every tick; others keep the value that was last written.

type Parameters Result
sine min, max, period, phase, noise Sine wave between min and max
random min, max Uniform noise
random_walk min, max, step Bounded random walk
expr expr Expression over other points of the same device, e.g. temperature > 26
follow target (point name or expression), tau, noise First-order lag toward another point
ramp target, rate (number or expression) Rate-limited tracking of another point (units per second)
counter rate (number or expression, per second) Integrates the rate, e.g. energy from power; integer types wrap around at their limit
pulse rate (pulses per second) Integer pulse counter
replay file, column, interpolate, loop, offset Plays a CSV column on the simulated clock

Values written by a Modbus master or from the UI are validated against the data type, min / max and access.

Templates

A template generates a device's points, with addresses allocated automatically, and couples devices through params (for example a PCS references its BMS). Add one with template: <name> and your own params; points of the same name in the device override the template's.

Template Content
battery_pcs Run command, P / Q set points with ramp, actual P / Q, DC voltage, SOC limits, status
bms SOC integrated from the PCS power, SOH, cell voltage / temperature, alarms
power_meter Three-phase voltage / current / power, frequency, energy counters
env_sensor Temperature and humidity
custom Empty device, define all points yourself

sme-modbus-sim templates lists the parameters. The templates are generic and original; no vendor register maps are built in. sunspec_pv_inverter, sunspec_meter, sunspec_der and sunspec_battery are generated from the public SunSpec model definitions (Apache-2.0) and implement SunSpec Modbus models (not affiliated with, endorsed by, or certified by SunSpec Alliance). Import your own vendor maps privately via Excel or user-local templates.

User-local templates

Your own templates live outside the installation, in a directory of YAML files: --templates-dir DIR on the command line, else $SME_MODBUS_SIM_TEMPLATES, else ~/.sme-modbus-sim/templates/. They are loaded at startup (before the configuration, so devices can use them) and again with Templates › Reload user templates (POST /api/templates/reload). A user template with the name of a built-in template replaces it. A file with errors is skipped and reported; it never stops the simulator.

# ~/.sme-modbus-sim/templates/my_inverter.yaml
name: my_inverter          # default: the file name
title: My PV inverter
description: Register map of our inverter
params: {rated_kw: 10}     # defaults; a device overrides them with params:
points:                    # same schema as a device's points:
  - {name: p_limit, table: holding, address: 0, datatype: uint16, scale: 0.1, max: "{rated_kw}"}
  - {name: p_actual, table: input, address: 0, datatype: int16, scale: 0.1,
     behavior: {type: expr, expr: "min(p_limit, {rated_kw} * 0.8)"}}

Parameters are substituted only inside string values with Python str.format rules: {rated_kw} is replaced by the parameter value. A string that is exactly one placeholder ("{rated_kw}") takes the value with its type, so it works in numeric fields. Write literal braces as {{ and }}.

Save as template in the device header (POST /api/templates/from-device/{device} with {"name": ..., "overwrite": false}) writes the device's expanded points as a template file into this directory, for example after importing a vendor register map from Excel. GET /api/templates marks each template with source (builtin / user) and, for user templates, the file path.

SunSpec templates

sunspec_pv_inverter, sunspec_meter, sunspec_der and sunspec_battery are templates generated from the public SunSpec model definitions (Apache-2.0, vendored unmodified from sunspec/models at commit 90b4a331dcca1d6eac69c1bead952fddcc5852e0); they implement SunSpec Modbus models. Not affiliated with, endorsed by, or certified by SunSpec Alliance.

Template Models Params
sunspec_pv_inverter 1, 103, 120, 121, 122, 123, 160 rated_w, mppt_count, ac_voltage_v, frequency_hz, dc_voltage_v, serial_number, base_address
sunspec_meter 1, 203 base_load_w, voltage_v, frequency_hz, pv_device, serial_number, base_address
sunspec_der 1, 701, 702, 703, 704, 705 rated_w, ac_voltage_v, frequency_hz, vv_curves, vv_points, serial_number, base_address
sunspec_battery 1, 802, 803 capacity_wh, max_w, dc_voltage_v, initial_soc, string_count, der_device, serial_number, base_address
  • Holding registers from base_address (40000, 0 or 50000): SunS marker, each model (ID, L, points), end model (0xFFFF, L = 0). Point names are m<id>_<Name> (e.g. m103_W); repeating groups are m160_module1_DCW, ...
  • Scale factors: datatype sunspec_sf (int16) and point field scale_ref: <sf point>; the engineering value is raw x 10^sf, with the sf read from the referenced point at encode / decode time.
  • Not implemented values (0x8000 int16 / sunssf, 0xFFFF uint16, 0x80000000 int32, 0xFFFFFFFF uint32, NaN float32) appear as null in the UI and API (point field nullable: true). Optional model points without a value are left not implemented; accumulators are never null.
  • Inverter: m103_W follows a daylight curve, capped by m123_WMaxLimPct when m123_WMaxLim_Ena = 1, and 0 when m123_Conn = 0; m103_WH accumulates; m103_St = OFF / SLEEPING / MPPT. Meter: m203_W = load profile minus pv_device's m103_W (> 0 import), m203_TotWhImp / m203_TotWhExp accumulate.
  • DER (sunspec_der): m701_W ramps toward the daylight curve, or toward m704_WSet (W) / m704_WSetPct (% of m702_WMax) when m704_WSetEna = 1 (negative = absorb, down to -m702_WChaRteMax); capped by m704_WMaxLimPct when m704_WMaxLimPctEna = 1; increases limited by m704_WRmp (% of m702_WMax per second); 0 when m703_ES = 0. m701_Var follows m704_VarSet / m704_VarSetPct (per m704_VarSetMod) when m704_VarSetEna = 1. m701_TotWhInj / m701_TotWhAbs accumulate. Model 705 holds vv_curves curves of vv_points points (nested repeating groups; NCrv / NPt set accordingly) with an illustrative default curve.
  • Battery (sunspec_battery): m802_W (simulator convention: > 0 discharge, < 0 charge, as model 701 W) follows a demo day profile or der_device's m701_W, stops at m802_SoCMin / m802_SoCMax and when m802_SetOp = 2 (DISCONNECT); m802_SoC integrates m802_W over m802_WHRtg; m802_ChaSt, m802_V, m802_A, cell voltages and the model 803 string points are derived from it.
  • Not supported (registers are readable / writable but have no effect): reversion timers (*Rvrt*), power-factor setpoints (m704_PFW*), reactive-power priority, volt-var curve execution (m705_Ena, AdptCrvReq), enter-service thresholds / delays, anti-islanding, m802_SetInvState, heartbeat supervision (m802_CtrlHb), alarm reset. Their detailed semantics are not defined in the model definitions.